Tools UPS Sizing & Runtime Calculator

UPS Sizing & Runtime Calculator

Size a UPS from your load in watts with proper headroom, or estimate battery runtime from Ah and voltage. Honest derating for inverter loss and high-rate discharge. Free.

VA vs watts, and why runtime is separate

UPS units are sold by VA (apparent power) but your gear draws watts (real power). VA = watts ÷ power factor, and modern power-factor-corrected IT loads sit around 0.9–1.0. Size so your real load lands at or below ~80% of the UPS rating — running a UPS flat-out shortens both its battery life and its ability to handle inrush.

Runtime is a different question entirely. It's set by the battery, not the VA rating, which is why two UPS units of the same VA can have very different runtimes. A UPS holds your load up long enough for a graceful shutdown or a generator to start — most double-conversion and line-interactive units give only a handful of minutes at full load by design.

Typical load Approx. watts Suggested UPS
Single desktop + monitor 150–300 W 650–850 VA
Small NAS + network gear 100–200 W 650–1000 VA
Wall-mount rack (switch, firewall, NAS) 300–500 W 1000–1500 VA
Half-rack of servers 800–1500 W 2200–3000 VA

Planning UPS coverage for a server room or closet? See UPS sizing for a small-business server room for load auditing, runtime targets, and when to step up to an external battery pack.